Goodrive350-19 series VFD Troubleshooting
- 391 -
Replace or change the wiring to
enhance anti-interference
capacity
Poor contact of the
connector of control board;
Hall component is damaged;
Exception occurred to
amplification circuit
Check the connector and
re-plug;
Replace the hall component;
Replace the main control board
Motor capacity does not
match with the VFD capacity,
this fault may occur easily if
the difference between them
is exceeds five power
classes;
Motor parameter is set
improperly;
The parameters gained from
autotuning deviate sharply
from the standard
parameters;
Autotuning timeout
Change the VFD model, or
adopt V/F mode for control;
Set proper motor type and
nameplate parameters;
Empty the motor load and carry
out autotuning again;
Check motor wiring and
parameter setup;
Check whether upper limit
frequency is larger than 2/3 of
the rated frequency
R/W error occurred to the
control parameters;
EEPROM is damaged
Press STOP/RST to reset;
Replace the main control board
PID feedback offline
fault
PID feedback offline;
PID feedback source
disappears;
Check PID feedback signal
wires;
Check PID feedback source
Brake circuit fault or brake
tube is damaged;
The resistance of external
braking resistor is too small
Check the braking unit, replace
with new brake tubes;
Increase brake resistance