EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 81

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Commissioning
- 74 -
Function
code
Name
Description
Default
release
The value 0 indicates the delay after
forward brake release is used.
P90.24
Delay before forward brake
closing
0.0005.000s
0.300s
P90.25
Delay before reverse brake
closing
0.0005.000s
The value 0 indicates the delay
before forward brake closing is used.
0.000s
P90.26
Delay after forward brake
closing
0.0005.000s
0.300s
P90.27
Delay after reverse brake
closing
0.0005.000s
The value 0 indicates the delay after
forward brake closing is used.
0.000s
P90.28
Maintenance frequency for stop
0.0050.00Hz
5.00Hz
P90.29
Maintenance frequency hold
time for stop
0.005.000S
0.000s
P90.30
Torque verification fault
detection time
0.0010.000S
3.000s
P90.31
Enabling the monitoring on
brake status
01
0: Disable
1: Enable the brake current
monitoring (and brake feedback
detection)
After the brake is enabled, the brake
status monitoring function can be
enabled.
In open-loop mode: If a brake
feedback exception occurs, a fault is
reported after the brake feedback
exception delay P90.32.
In closed-loop mode: During the stop,
if a brake feedback exception occurs,
a fault is reported after the brake
feedback exception delay P90.32.
During running, if a brake feedback
exception occurs, the current is
monitored after the brake feedback
exception delay P90.32. If the
present current is less than the
0

Table of Contents

Related product manuals