33
The compressor does not work
The compressor works
but it does not cool the cell
The condensing fan
does not work
The evaporator
does not defrost
No power supply
Check connection
of electrical line
Auxiliary circuit protection
fuses blown
Replacement of fuses
by authorised technician
Intervention of internal
Klixson for overload
Intervention of a technician
Circuit breaker
switch tripped
Intervention of a technician to rearm
switch and check calibration
Pressure switch intervention
for high pressure
Electronic diagnostic control (ALP alarm).
Intervention of a technician
Relay board
consent missing
Intervention of a technician
to replace circuit board
Remote switch broken
Intervention of a technician
to replace remote switch
No refrigerant gas
Intervention of a technician
No power supply
Check connection
of electrical line
Pressure switch broken
Intervention of a technician
to replace device
Fan broken
Intervention of a technician
to replace fan
Start condenser broken
Intervention of a technician
to replace start condenser
Compressor remote switch
consent missing
Intervention of a technician
to replace compressor remote switch
Control defrost cycle
programming
Wrong defrost cycle
programming
Electrovalve broken
Intervention of a technician
Condenser dirty Pulire batteria condensante
Intervention of a technician
to replace electrovalve or coil
Liquid line electrovalve broken
NON electronically-managed diagnostics:
Malfunction
The front board does not turn on
The cell fans do not turn
No power supply
Check connection
of electrical line
No power supply
Check connection
of electrical line
Fan broken
Intervention of a technician
to replace fan
Relay board broken
Intervention of a technician
to replace board
Protection fuses blown
Replacement of fuses by
authorised technician
Possible cause Possible solution
Bus connector between
two boards disconnected
Insert Bus cable in dedicated connector
both in the Front board
and in the Relay board
DescriptionCode
AS1
S1 cell probe faulty
S1 probe broken Replace S1 probe
AS2
S2 cell probe faulty
S2 probe broken Replace S2 probe
AS3
Total block with probes
S1 and S2 faulty
Probes S1 and S2 are broken Probes S1 and S2 are broken
Possible cause Possible solution