EasyManua.ls Logo

ITV Greenline HE E6-E11 - 13 Function Check; Refrigerant Circuit; Filling Pressure in Collector Circuit; Setting Heating System

Default Icon
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function check
6 720 802 419 (2012/06) en
42
13 Function check
13.1 Refrigerant circuit
When the heat pump starts and there are quick changes in temperature,
bubbles may become visible in the sight glass Æ Figure 41.
Fig. 41
In the event of constant formation of bubbles:
B Contact a service representative.
13.2 Filling pressure in collector circuit
The level in the vessel should not fall below the min-level 1/3. If the fluid
level is too low fill in as below:
The heat pump must be running all the time while filling.
B Remove the cover on the valve on top of the tank. Now carefully open
the valve.
B Check that the valve is fully open.
B Fill with anti-freeze (to 2/3) with the help of a clean watering can or
similar.
B Close the valve and finish by screwing on the cover.
13.3 Setting heating system operating pressure
B When the gauge is below 0.5 bar (in cold installation): Fill water until
the gauge shows approx 1 bar again.
B If there is a pressure drop: check the expansion vessel and heating
system for leaks.
13.4 Operating temperatures
Check the temperatures in the heat carrier and collector circuit after 10
minutes of operation:
Temperature difference between heating system flow and return
approx. 7 ... 10 K.
Temperature difference between collector circuit in and out approx. 2
... 5 K, recommendation: 2 ... 3 K.
When the temperature difference is too small:
B Reduce the speed of the corresponding circulation pump (G2 or G3)
in order to obtain a lower flow.
When the temperature difference is too great:
B Increase the speed of the corresponding circulation pump (G2) in
order to obtain a greater flow.
Fig. 42
[P2] Heat carrier pump G2
[P3] Collector circuit pump G3
[t
SA
]Temperature collector circuit out T11
[t
SE
]Temperature collector circuit in T10
[t
HV
]Temperature heat transfer fluid out T8
[t
HR
]Temperature heat transfer fluid in T9
The refrigerant circuit may only be opened by authorised
service engineers with refrigeration authorisation.
DANGER: Risk of toxic fumes!
The refrigerant circuit contains substances which, when
released or exposed to open fire, can form toxic fumes.
The fumes block the airways even at low concentrations.
B If the refrigerant circuit is not air-tight, the room must
be vacated immediately and properly aired.
6 720 641 855-09.1I
Pressure gauge reading
0.5 bar Minimum system pressure (when cold)
1 bar Normal filling pressure
1.5 bar Maximum system pressure at highest heating water
temperature:
must not be exceeded (safety valve opens).
Table 21
0 K
10 K
7 K
6 K
9 K
P2
P2
P2
t
HV
- t
HR
3 K
5 K
2 K
P3
P3
P3
P3 ( )
P2 ( )
P2 ( )
t
SE
- t
SA
6 720 612 299-04.3O

Table of Contents