Operation Manual – ITW GSE 7400 Battery Powered GPU
90 kVA
Setup Lock / Output Mode / Compensation
Document No. 575.410DB Page 89 of 195
7.16 Engine Start SoC
This set of submenus allows the user to adjust the Engine Start SoC, to set the % (10 to 50%) of when
the Range Extender Engine should automatically start, if it’s installed.
Enter the Setup menu, and then scroll up or down to the Engine Start SoC submenu. Press the center
● button to enter the submenu, and then press the ● button again to allow the value to be changed.
Press the up or down arrow buttons to change the selection. Press the center ● button to record the
new value. Press the left arrow button to exit the submenu and return to the submenu list.
7.17 Real Time Clock Setup
This set of submenus allows the user to adjust the internal clock to the correct local time.
Enter the Setup menu, and then scroll up or down to the Real Time Clock Setup submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the left arrow button to exit the submenu and return to the submenu list.
7.18 Date / Time Format
The date and time format that is displayed on all screens and reports can be adjusted using this
submenu. The selection is 24-hour clock and DD:MM:YYYY date format, or 12-hour clock with the
MM:DD:YYYY date format.
Enter the Setup menu, and then scroll up or down to the Date / Time Format submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the left arrow button to exit the submenu and return to the submenu list.
7.19 Ethernet Configuration
This set of submenus allows the user to enter the Ethernet IP address, subnet mask, gateway address,
and DNS1 values for TCP/IP communications with a BMS or RMS central monitoring system.
Enter the Setup menu, and then scroll up or down to the Ethernet Configuration submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the left arrow button to exit the submenu and return to the submenu list.