Page 9
ENGLISH
Jandy
®
Pro Series VS PlusHP Pumps
|
Installation & Operation Manual
CAUTION
Failuretoprovidedataplatevoltage(within10%)during
operation will cause the motor to overheat and void
the warranty.
3.2.2 Bonding and Grounding
1. In addition to being properly grounded and in
accordance with the requirements of the National
Electrical Code (NEC), or in Canada the Canadian
Electrical Code (CEC), the pump motor must
be bonded to all metal parts of the swimming
pool, spa or hot tub structure and to all electrical
components and equipment associated with the
pool/spa water circulation system.
2. The bonding must be accomplished by using a
solid copper conductor, No. 8 AWG or larger. In
Canada No. 6 AWG or larger must be used. Bond
the motor using the external bonding lug provided
on the motor frame.
WARNING
Always disconnect the power source before working
on a motor or its connected load.
WARNING
Make sure that the control switch, time clock, or control
system is installed in an accessible location, so that in
theeventofanequipmentfailureoralooseplumbing
fitting,theequipmentcanbeturnedoff.Thislocation
must not be in the same area as the pool pump, filter,
andotherequipment.
CAUTION
The pump must be permanently connected to a
dedicatedelectricalcircuit.Nootherequipment,
lights, appliances, or outlets may be connected to the
pump circuit, with the exception of devices that may
berequiredtooperatesimultaneouslywiththepump,
such as a chlorinating device or heater.
GROUND
NEUTRAL
Breaker Panel
GFCI
Pump
L1
L2
Terminal Block
Figure 4. Bonding the Motor
3.2.3 Electrical Wiring
1. The pump motor must be securely and adequately
grounded using the green screw provided. Ground
before attempting to connect to an electrical power
supply. Do not ground to a gas supply line.
2. Wire size must be adequate to minimize a voltage
drop during the start-up and operation of the pump.
3. Insulate all connections carefully to prevent
grounding or short-circuits. Sharp edges on
terminals require extra protection. For safety,
and to prevent entry of contaminants, reinstall all
conduit and terminal box covers. Do not force
connections into the conduit box.
3.2.4 Controller Options
The pump can be operated by one (1) of four (4)
controllers,
JEP-R variable-speed controller, AquaLink RS,
AquaLink PDA or AquaLink Z4.
The pump communicates with the controllers via a four-
wire RS-485 interface.
NOTE Since the pump is operated by an external
controller the pump will not be turned on until it
is turned on with a controller.
3.2.4.1 Install with AquaLink
®
controller
The VS PlusHP pump can be operated by the following
AquaLink Controllers:
• AquaLink RS (Rev O or later)
• AquaLink PDA (Rev 4.0 or later)
• AquaLink Z4
1. Disconnect the high voltage lines or open any
breaker to which the pump power is connected.
WARNING
ELECTRICAL SHOCK HAZARD
Turn off all switches and the main breaker in
the variable-speed pump electrical circuit before
starting the procedure. Failure to comply may
cause a shock hazard resulting in severe personal
injury or death.
2. Dip switches 1 and 2 need to be in the OFF
position. See “Figure 5. Wiring AquaLink RS,
PDA or Z4”.
3. Select the desired address(es) by setting dip
switches 3 and/or 4, as shown in “Table 2. Dip
Switch Settings”
4. Disconnect the RS-485 cable from the 4-pin
header on the pump drive.
NOTE: Do not cut the cable or you will lose the ability to
returntothedefaultfactoryconguration
5. Connect the new RS-485 cable from the AquaLink
through the available compression tting and
route the 4-conductor cable through the motor
drive threaded port closest to the connector. See
““Figure 5. Wiring AquaLink RS, PDA or Z4”