EasyManuals Logo

janitza UMG 96 RM-EL User Manual

janitza UMG 96 RM-EL
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
62
UMG 96RM-EL
Fig. Error message
Error messages
The UMG 96RM-EL shows three different error messages
on the display:
- warnings,
- serious error and
- metering range exceedances.
If there are warnings and serious errors, the error
message is indicated by the symbol "EEE" followed by
an error number.
The three-digit error number is composed of the error
description and (if detectable by the UMG 96RM-EL)
one or more error causes.
Symbol for an error
message
Error number
Symbol for an error
message
Description of the error
Error cause
Example of error message 911:
The error number is composed of serious error 910
and internal error cause 0x01.
In this example, an er-
ror occurred when read-
ing the calibration from
the EEPROM. The device
must be sent to the manu-
facturer for inspection.