Table 9: Status LEDs and descriptions of LED States
LED label LED color Normal LED state Description of LED states
POWER Green On Steady Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is
open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
FAULT Red Off Steady Two blinks followed by long pause = Controller powered on in default state. For
more information about this default state, see Input/Output Wiring Validation.
Off Steady = No Faults
On Steady = Device Fault or no application loaded
Blink - 2 Hz = Startup in progress, not ready for normal operation
Rapid blink = SA Bus communications issue
SA BUS Green Blink - 2 Hz Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
ETH1 Green Off Off Steady = ETH1 is not connected
Blinking = ETH1 connected and communicating
ETH2 Green Off Off Steady = ETH2 is not connected
Blinking = ETH2 connected and communicating
Repair information
If the controller fails to operate within its specifications,
replace the controller. For a replacement controller,
contact your Johnson Controls representative.
FAC4911 accessories
Note: The accessories marked with an asterisk (*) in the table are not qualified for use with a UL 864 UUKL/UUKLC
10th Edition Listed Smoke Control system.
Table 10: FAC4911 accessories
Product Code Number Description
IOM Series Expansion
Modules
Refer to the Metasys System Field Equipment Controllers and Related Products Product Bulletin
(LIT-12011042) for a complete list of available IOM Series Expansion Modules.
XPM Series Expansion
Modules
Refer to the Metasys CGx, CVx Equipment Controllers and XPM Expansion Modules Product
Bulletin (LIT-12013105) for a complete list of available XPM series expansion modules.
TL-CCT-0 Controller Configuration Tool (CCT) software
MS-FCP-0 Metasys Field Controller Firmware Package Files for CCT
Mobile Access Portal
(MAP) Gateway*
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the
appropriate product for your region.
NS Series Network
Sensors
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor model
descriptions.
TP-2420* Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
MS-DIS1710-0* Local Controller Display, 3.0 in. (76 mm) monochrome display with navigation keypad. Refer
to Local Controller Display Product Bulletin (LIT-12011273) for more information.
M4-DLK0350-0* Local Controller Display with 3.5 in. (89 mm) color display and navigation keypad. For more
information, refer to DLK0350 Product Bulletin (LIT-12014001).
WRZ Series Wireless
Room Sensors*
Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12011653) for specific
sensor model descriptions.
WRZ-7860-0* Receiver for One-to-One Wireless Room Sensing Systems - functions with WRZ Series Sensors
room sensors. Refer to the WRZ-7860 Receiver for One-to-One Wireless Room Sensing Product
Bulletin (LIT-12011640) for a list of available products.
FAC4911 Advanced Application Field Equipment Controller Installation Guide 19