EasyManuals Logo

Johnson Controls Frick 852 User Manual

Johnson Controls Frick 852
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
RWH ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.620-IOM (DEC 12)
Page 18
Booster Compressor Loading: The compressor loads when
MSV solenoid YY2 is energized and oil ows from the oil
manifold through valve ports P and B to cylinder port SC2
and enters the load side of the cylinder. Simultaneously, oil
con tained in the unload side of the cylinder ows out cylinder
port SC1 through valve ports A and T to com pressor suction.
Booster Compressor Unloading: The compressor un loads
when MSV solenoid YY1 is energized and oil ows from the
oil manifold through valve ports P and A to cylinder port SC1
and enters the unload side of the cylinder. Simultaneous ly,
oil contained in the load side of the cylinder ows out of
compressor port SC2 through valve ports B and T to com
pressor suction.
NOTICE
To control the rate of loading and unloading, change
cycle time, proportional band, and dead band setpoints
with Quantum control. If additional control is needed,
throttle SC2 or BP.
Figure 22
WARNING
NEVER open valve BP and valve SC2 at the same time
during compressor operation.
VOLUME RATIO CONTROL
NOTICE
See Figure 23 for port references.
Open valve at SC3
Open valve at T1
Compressor Vi increase: The volume ratio Vi is increased
when MSS solenoid valve YY3 is energized and oil ows from
the oil manifold through valve ports P and A to compres
sor port SC3, enters the increase side of the cylinder and
overcomes the decrease spring tension. Simultaneously, oil
ows from T1 port through valve ports B and T to compres
sor suction. The inboard side of the slide stop piston is at
suction pressure.
Compressor Vi decrease: The volume ratio Vi is decreased
when MSS solenoid valve YY4 is energized and oil ows from
the oil manifold through valve ports P and B to compressor
port T1, enters the decrease side of the cylinder. Simultane
ously, oil ows form SC3 port through valve ports A and T
to compressor suction. On these models, YY4 is energized
which permits oil to vent from port A to T with assistance
from the unloader spring.
TO CONTROL THE RATE OF VI CHANGE, THROTTLE THE
NEEDLE VALVE AT SC3 PORT.
COMPRESSOR OIL COOLING SYSTEMS
The RWH unit can be equipped with one of several systems
for controlling the compressor oil tempera ture. They are
single or dualport liquid injection and thermo syphon, air
cooled or watercooled oil coolers. Each system is autom
ati cally controlled, independent of compressor loading or
unloading.
Oil cooling systems should maintain oil temperature within
the following ranges for R717:
Liquid Injection External*
Oil Cooling Oil Cooling
130  170°F 120  160°F
* Thermosyphon oil cooling (TSOC), aircooled, or water
cooled oil cooling (WCOC).
SINGLE-PORT LIQUID INJECTION
The singleport liquid injection system is desig ned to permit
liquid refrigerant injection into one port on the compressor
at any given moment and operates as outlined.
The liquid injection control valve is enabled by the micro
processor when the temperature sensor, in stalled in the
compressor discharge, exceeds the setpoint. Highpressure
liquid refriger ant is then expanded through the tempera
ture control valve (TCV) and cools the compressor. Refer to
P & I DIAGRAMS section for piping and instrumentation
drawings.
DUAL-PORT LIQUID INJECTION
The dualport liquid injection system is design ed to obtain
the most efcient compressor performance at high and low
compression ratios by permitting injection of liquid refriger ant
into one of two ports optimally located on the com pressor.
This minimizes the performance penalty incurred with liquid
injection oil cooling.
The dualport system contains all the com ponents of the
singleport system with the addition of a directional valve
and operates as follows:
The liquid injection solenoid valve is energized by the
micro processor when the temperature sensor, in stalled in
the oil manifold, exceeds the setpoint. Liquid refrigerant is
then passed through the tempera ture control valve (TCV)
to the directional solenoid valve. Depending on the com
pressor’s operating volume ratio (Vi), the micropro cessor
will select the ow of the liquid refrigerant to the optimum
com pressor port.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Frick 852 and is the answer not in the manual?

Johnson Controls Frick 852 Specifications

General IconGeneral
BrandJohnson Controls
ModelFrick 852
CategoryCompressor
LanguageEnglish