EasyManuals Logo

Johnson Controls Frick 852 User Manual

Johnson Controls Frick 852
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
RWH ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.620-IOM (DEC 12)
Page 21
Using the chart below, as long as the control input
is 155°F the output will be at 20% with proportional
control only. Integral control will increase the output
in increments, over time, to correct the control input
to the setpoint.
Control Input Output %
150°F 0%
155°F 20%
160°F 40%
165°F 60%
170°F 80%
175°F 100%
Based on these descriptions set PID #1 for EZ-Cool
LIOC
per Figure 25 as a starting point. Tuning of the output will be
required. There should be no need to use a derivative gain.
SUCTION CHECK VALVE BYPASS
The RWH unit is equipped with a lowpressuredrop suction
check in the suction piping. Units that have an 8" or larger
stop angle or globe valve should be piped as shown in the
shaded area of Figure 25. During normal operation, valve
NV1 is closed. This is a pumpout connection to allow re
frigerant removal to the system suction prior to evacuation
for servicing. Valve NV2 must be open in most systems
at all times. It should normally be cracked open to allow
the oil separator to slowly bleed down to approximately
system suction pressure when the unit is stopped (having
this valve cracked open allows the compressor drive mo
tor to have an easier start, and the discharge check valve
will seat more tightly). If the drive coupling backspins, start
closing the valve until the backspin stops. If the separator oil
level foams excessively on shutdown, NV2 should be closed
slightly. If the separator takes more than 20 – 30 minutes to
equalize to suction pressure after shutdown, NV2 can be
opened slightly. See Figure 26.
Check valve CV is installed on all RWH packages. On high
stage systems, check valve CV is installed with a 45 psi
spring to avoid the possibility of backfeeding to a shutdown
compressor from a common economizer vessel.
On booster systems, check valve CV is installed with a 25 psi
spring to avoid the possibility of air ingress into the system,
if the system suction pressure is below atmospheric.
Figure 26 - Suction Check Valve Bypass
LOW AMBIENT OPERATION
It is recommended that oil separators be insulated as a
minimum requirement to preserve the heat generated by
the oil heaters. It is important that the coalescer end of the
separator be insulated to prevent refrigerant condensation.
On systems located outdoors or in unheated buildings where
the ambient temperature could drop below +40°F, insulating
and/or heat tracing of the compressor lube oil systems is
highly recommended.
When low ambient temperatures (below +20°F) are a pos
sibility, it is recommended that lube oil lines, oil lters, oil
pumps, and oil coolers be heat traced and insulated.
Freezeup protection must also be provided for all water
cooled equipment
BALANCE PISTON PRESSURE REGULATOR
A Balance Piston Pressure Regulator may be required to
reduce the extended overbalance from the thrust balance
piston at part load.
High-Stage SB-2 Oil Supply Line Diagram, Figure 27, shows
the three additions described below arranged in parallel.
Figure 27 - High-Stage SB-2 Oil Supply Line Diagram
PRESSURE-REGULATING VALVE: Discharge pressure deter
mines compressor thrust balance. The proper setting for the
pressureregulating valve is 50 psi (±15) below DISCHARGE
pressure when slide valve is less than 65%.
SOLENOID VALVE: Energizing, or opening, the solenoid valve
pressurizes the balance piston with full oil pressure from the
oil manifold, bypassing the A4ALE Pressure Regulating Valve.
Deenergizing, or closing, the solenoid valve pressurizes
the balance piston with oil pressure regulated by the A4ALE
Pressure Regulating Valve. The solenoid valve is not always
required. Refer to project prints and documents.
Signals from the control panel operate the solenoid valve
(output module 12 on micro panel). The solenoid valve should
open when the slide valve position is 70% or greater, and
close when the slide valve position is 65% or less. These
setpoints may vary from project to project. Refer to project
documentation.
ORIFICE: The orice ensures oil supply to the inlet end bear
ings during upset conditions such as startup.
INITIAL START-UP
Initial start-up must be performed under the super vision
of a Johnson Controls-Frick authorized start-up represen-
tative to prevent voiding the compressor warranty. Prior
to the start-up, the prestart check must be accomplish ed.
See Prestart Checklist in the Forms section of this manual.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Frick 852 and is the answer not in the manual?

Johnson Controls Frick 852 Specifications

General IconGeneral
BrandJohnson Controls
ModelFrick 852
CategoryCompressor
LanguageEnglish