QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 61
DIGITAL BOARD VALUES: (Read Only, Continued)
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data
Digital
Board #
Channel
#
Module
Type
1063 N10:63 41064 R User Defined Digital Input #1 1 17
Input
Input
1064 N10:64 41065 R User Defined Digital Input #2 1 18
1065 N10:65 41066 R User Defined Digital Input #3 2 9
1066 N10:66 41067 R User Defined Digital Input #4 2 10
1067 N10:67 41068 R User Defined Digital Input #5 2 11
1068 N10:68 41069 R User Defined Digital Input #6 2 12
1069 N10:69 41070 R User Defined Digital Input #7 2 13
1070 N10:70 41071 R User Defined Digital Input #8 2 14
1083 N10:83 41084 R User Defined Digital Output #1 2 7
Output
1084 N10:84 41085 R User Defined Digital Output #2 2 8
1085 N10:85 41086 R User Defined Digital Output #3 2 18
1086 N10:86 41087 R User Defined Digital Output #4 None 0
1087 N10:87 41088 R User Defined Digital Output #5 None 0
1088 N10:88 41089 R User Defined Digital Output #6 None 0
1089 N10:89 41090 R User Defined Digital Output #7 None 0
1090 N10:90 41091 R User Defined Digital Output #8 None 0
1091 N10:91 41092 R User Defined Digital Output #9 None 0
1092 N10:92 41093 R User Defined Digital Output #10 None 0
1093 N10:93 41094 R Main Oil Injection None 0
1094 N10:94 41095 R Liquid Level Increase None 0
1095 N10:95 41096 R Liquid Level Decrease None 0
1096 N10:96 41097 R PLC Interlock None 0
1097 N10:97 41098 R High VI Liquid Injection 1 10
1000 N10:100 41101 R Timed Digital Output A None 0
1101 N10:101 41102 R Timed Digital Output B None 0
1102 N10:102 41103 R Timed Digital Output C None 0
1103 N10:103 41104 R Discharge Butterfly Valve Solenoid None 0