QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 65
MODE VALUES:
CALCULATED VALUES: (Continued)
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data Units
3102 N31:02 43103 R Coalescer Filter Differential Pressure (Magnitude)
3103 N31:03 43104 R Calculated Superheat 1 Temperature (Magnitude)
3104 N31:04 43105 R Calculated Superheat 2 Temperature (Magnitude)
3105 N31:05 43106 R Calculated Superheat 3 Temperature (Magnitude)
3106 N31:06 43107 R Thousands of Vyper Drive Total KW Hours Real (#.##)
3107 N31:07 43108 R Units of Vyper Drive Total Kw hours Real (#.##)
3109 N31:09 43110 R Vyper Drive Max Load FLA Amps
3111 N31:11 43112 R Saturated Discharge Temperature Temperature
3112 N31:12 43113 R Wet Bulb Temperature Temperature
3113 N31:13 43114 R Wet Bulb Saturated Control Temperature Temperature
3118 N31:18 43119 R New Maintenance Event Flag
This register gets set to a
value of one when a main-
tenance event occurs and is
logged (can be read through
communications and gets
cleared when the user navi-
gates to the Events screen)
Note 1: Refer to the chart of WARNING/SHUTDOWN MESSAGE CODES on pages 103-107 to determine which message is being
displayed.
Note 2: To calculate the Total Run Time, use the following equation:
Total Run Time (Thousands) x 1000 + Total Run Time (Units) = Total Run Time
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Value Code
4000 N40:0 44001 R Compressor Status
0 = Off
1 = Running
20 = Starting
30 = Stopping
31 = Stopping - High Capacity
32 = Stopping – Pumpdown
33 = Stopping – Cool Down Period
4001 N40:1 44002 R Pump Type
0 = No Pump
1 = Full Time
2 = Cycling
3 = Demand
4 = Shaft Auxiliary
5 = Shaft
4002 N40:2 44003 R Prelube
0 = Not in Prelube
1 = In Prelube
4003 N40:3 44004 R Postlube
0 = Not in Postlube
1 = In Postlube
4004 N40:4 44005 R Shutdown
0 = No Shutdowns
1 = Shutdown
4005 N40:5 44006 R Warning
0 = No Warning
1 = Warning