QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 97
DBS SETPOINT VALUES (Continued):
GENERAL SETPOINT VALUES:
VSD (VYPER) SETPOINT VALUES:
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Units
8998 N119:98 48999 R Stall Time Setpoint Seconds
8999 N119:99 49000 R Jam Current Level Setpoint Percent (%)
9000 N120:00 49001 R Jam Run Delay Setpoint Seconds
9001 N120:01 49002 R DBS Service Factor Setpoint Percent (%)
9002 N120:02 49003 R Current Unbalance Alarm Level Setpoint
9003 N120:03 49004 R Current Unbalance Alarm Run Delay Setpoint Seconds
9004 N120:04 49005 R RTD Temperature Alarm Level Setpoint Temperature
9005 N120:05 49006 R RTD Temperature Trip Level Setpoint
9007 N120:07 49008 R DBS Command Flags None
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Units
9100 N121:00 49101 R/W Real Time Trending Recording Interval Seconds
9101 N121:01 49102 R/W History Trending Recording Interval Minutes
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Units
9200 N122:00 49201 R/W Vyper Drive Standby Time Minutes
9210 N122:10 49211 R Vyper Drive Auto Speed Command
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9211 N122:11 49212 R Vyper Drive Run Command None
9215 N122:15 49216 R Vyper Drive Current Fault None
9216 N122:16 49217 R Vyper Drive Current Warning
9218 N122:18 49219 R Vyper Drive Speed Command
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9219 N122:19 49220 R Vyper Drive Percent of Full Load Amps Percent (%)
9220 N122:20 49221 R Vyper Drive Actual Speed
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9223 N122:23 49224 R Vyper Drive Operating Mode
None
9224 N122:24 49225 R Vyper Drive Water Pump
9225 N122:25 49226 R Vyper Drive Precharge Relay
9226 N122:26 49227 R Vyper Drive Trigger SCRs
9228 N122:28 49229 R Vyper Drive Output Frequency Real
9229 N122:29 49230 R Vyper Drive Output Voltage
Integer
9230 N122:30 49231 R Vyper Drive DC Bus Voltage