QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 64
CALCULATED VALUES:
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data Units
3000 N30:0 43001 R Calculated Capacity Percent (%)
3006 N30:6 43007 R Filter Differential Pressure Pressure (Magnitude)
3008 N30:8 43009 R System Compression Ratio Percent (%)
3017 N30:17 43018 R New Event Flag
This register gets set to a
value of one when a general
event occurs and is logged
(can be read through com-
munications and gets cleared
when the user navigates to
the Events screen)
3018 N30:18 43019 R Current Runtime Hours
3019 N30:19 43020 R Suction Superheat
Temperature (Magnitude)
3020 N30:20 43021 R Discharge Superheat
3021 N30:21 43022 R Percent of Full Load Amps Percent (%)
3033 N30:33 43034 R Volume High End
Volts
3034 N30:34 43035 R Volume Current Value
3035 N30:35 43036 R Volume Low End
3036 N30:36 43037 R Capacity High End
3037 N30:37 43038 R Capacity Current Value
3038 N30:38 43039 R Capacity Low End
3039 N30:39 43040 R Calculated Volume Ratio Real
3058 N30:58 43059 R Calculated Volume Ratio (Suction)
Real
3059 N30:59 43060 R Calculated Volume Ration (Economizer)
3060 N30:60 43061 R Current Regulation Value Pressure
3061 N30:61 43062 R Current Regulation Setpoint
3062 N30:62 43063 R Estimated Kilowatts kW
3063 N30:63 43064 R Panel Temperature Temperature
3070 N30:70 43071 R Safety #1 Message (Most Recent)
Note
1
Integer
3071 N30:71 43072 R Safety #2 Message
3072 N30:72 43073 R Safety #3 Message
3073 N30:73 43074 R Safety #4 Message
3074 N30:74 43075 R Safety #5 Message
3075 N30:75 43076 R Safety #6 Message
3076 N30:76 43077 R Safety #7 Message
3077 N30:77 43078 R Safety #8 Message
3078 N30:78 43079 R Safety #9 Message
3079 N30:79 43080 R Safety #10 Message
3080 N30:80 43081 R Total Run Time (Thousands)
Note
2
Real
3081 N30:81 43082 R Total Run Time (Units)