ANALOG BOARD VALUES: (Continued)
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data
Analog
Board #
Channel
#
Module
Type
2059 N20:59 42060 R Analog Output #1 1 3
Output
2060 N20:60 42061 R Analog Output #2 None 0
2061 N20:61 42062 R Analog Output #3 None 0
2062 N20:62 42063 R Analog Output #4 None 0
2063 N20:63 42064 R Analog Output #5 None 0
2064 N20:64 42065 R Analog Output #6 None 0
2065 N20:65 42066 R Analog Output #7 None 0
2066 N20:66 42067 R Analog Output #8 None 0
2067 N20:67 42068 R Manifold Pressure 2 3
Input
2068 N20:68 42069 R Remote Capacity Position 1 13
2069 N20:69 42070 R Compressor VFD 2 3 Output
2070 N20:70 42071 R Liquid Level None 0
Input
2071 N20:71 42072 R Compressor Vibration - Suction 1 17
2072 N20:72 42073 R Compressor Vibration - Discharge 1 18
2073 N20:73 42074 R Motor Vibration - Shaft Side 1 19
2074 N20:74 42075 R Motor Vibration - Opposite Shaft Side 1 20
2075 N20:75 42076 R Condenser Analog Step #1 1 5
Output
2076 N20:76 42077 R Condenser Analog Step #2 1 6
2077 N20:77 42078 R Motor Temperature - Shaft Side None 0
Input
2078 N20:78 42079 R Motor Temperature – Opposite Shaft Side None 0
2079 N20:79 42080 R Motor Stator #1 Temperature 1 21
2080 N20:80 42081 R Motor Stator #2 Temperature 1 22
2081 N20:81 42082 R Motor Stator #3 Temperature 1 23
2082 N20:82 42083 R Superheat Output #1 None 0
Output
2083 N20:83 42084 R Superheat Output #2 None 0
2084 N20:84 42085 R Superheat Output #3 None 0
2085 N20:85 42086 R Analog output #10 None 0
2086 N20:86 42087 R Analog output #10 None 0
2087 N20:87 42088 R Analog output #11 None 0
2088 N20:88 42089 R Analog output #12 None 0
2089 N20:89 42090 R Analog output #13 None 0
2090 N20:90 42091 R Analog output #14 None 0
2091 N20:91 42092 R Analog output #15 None 0
2092 N20:91 42093 R Analog output #16 None 0
2097 N20:97 42097 R Discharge Butterfly Valve None 0
2098 N20:98 42098 R Vyper Coolant Temperature None 0
2099 N20:99 42099 R EZ Cool LIOC None 0
2100 N20:100 42100 R Vyper Cooling Control Output None 0
2101 N20:101 42101 R Outside Air Temperature None 0
2102 N20:102 42102 R Outside Relative Humidity None 0

Table of Contents