20 Operating Instructions—IFC-200 Operating Instructions
The following typical format displays Zones 95 or 96 (time control zones).
In addition to automatic activation of non-fire control points, this zone
may be used for detector day/night sensitivity select. If you want
day/night sensitivity for a smoke detector, Zone 95 or 96 must activate it.
When day/night sensitivity is active, detector sensitivity goes to the low
setting (3.00%) during the day.
OFF SOFTWARE ZONE
TIME CONTROL
ON=7:00 OFF18:00
DAYS=MTWTF H Z95
Where:
ON=7:00 OFF=18:00 indicates the programmed times that this zone
automatically turns on and off each day. The times are in 24 hour
(military) format.
DAYS= MTWTF H indicates the programmed days-of-week that the on/off
times are effective. “H” is a holiday, defined by Zone 97.
Note: To program midnight, enter 00:00. 24:00 is invalid.
The following typical format displays software Zone 97 (Holiday Zone):
OFF HOLIDAY ZONE 97
01/01 04/10 05/26
07/04 09/07 11/26
11/27 12/24 12/25
The numbers are day/month program selections for holiday days of the
year.
The following typical format is used to display software Zone 98 (coders):
OFF SOFTWARE ZONE
CODE TYPE:
MARCH TIME
Z98