Table 42: 5 ton heating charging chart for XA(F,H)*60H and JH(E,V)T*60H in downflow and horizontal right
Ambient
temperature
(°F)
60 47 40 30 17 10 0
CFM
Indoor
temperature
(°F)
60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80
1500
Liquid
pressure
(subcool)
390
(28)
439
(28)
489
(25)
366
(36)
416
(39)
466
(39)
353
(44)
404
(44)
456
(47)
331
(50)
385
(53)
437
(55)
308
(42)
355
(42)
400
(44)
295
(44)
342
(44)
387
(46)
286
(50)
331
(50)
375
(52)
1750
Liquid
pressure
(subcool)
365
(31)
414
(28)
463
(25)
345
(36)
392
(36)
445
(39)
333
(42)
384
(45)
436
(48)
319
(51)
369
(53)
417
(56)
290
(36)
333
(38)
381
(40)
279
(38)
324
(40)
367
(42)
270
(44)
314
(44)
357
(45)
2000
Liquid
pressure
(subcool)
342
(29)
390
(27)
439
(24)
325
(35)
375
(35)
424
(35)
314
(37)
365
(40)
416
(43)
306
(45)
352
(48)
398
(51)
278
(34)
324
(36)
370
(38)
270
(36)
313
(38)
356
(40)
261
(42)
304
(42)
347
(44)
-
Suction
pressure
113 116 118 94 95 97 81 83 85 68 68 68 48 49 49 41 42 43 34 34 35
Table 43: 5 ton heating charging chart for XA(F,H)*60J and JH(E,V)T*60J in upflow and horizontal left
Ambient
temperature
(°F)
60 47 40 30 17 10 0
CFM
Indoor
temperature
(°F)
60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80
1500
Liquid
pressure
(subcool)
317
(10)
357 (9) 397 (9)
295
(13)
336
(13)
378
(13)
285
(16)
326
(17)
367
(17)
271
(18)
309
(19)
348
(20)
254
(20)
291
(21)
328
(21)
245
(21)
283
(21)
320
(22)
235
(23)
272
(23)
310
(23)
1750
Liquid
pressure
(subcool)
298
(10)
338 (9) 377 (9)
281
(13)
319
(12)
362
(13)
273
(15)
312
(16)
352
(16)
261
(17)
298
(18)
337
(19)
245
(19)
282
(20)
320
(21)
237
(20)
274
(20)
311
(21)
228
(22)
265
(22)
303
(22)
2000
Liquid
pressure
(subcool)
279
(10)
318 (9) 357 (8)
266
(13)
306
(12)
345
(12)
261
(14)
298
(15)
336
(15)
250
(16)
287
(17)
325
(17)
236
(18)
273
(19)
311
(20)
229
(19)
265
(19)
302
(20)
221
(20)
258
(21)
295
(21)
-
Suction
pressure
114 116 118 94 95 96 82 82 82 68 68 67 52 52 52 44 44 45 36 37 38
Table 44: 5 ton heating charging chart for XA(F,H)*60J and JH(E,V)T*60J in downflow and horizontal right
Ambient
temperature
(°F)
60 47 40 30 17 10 0
CFM
Indoor
temperature
(°F)
60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80
1500
Liquid
pressure
(subcool)
319
(15)
359
(14)
399
(14)
297
(20)
338
(20)
380
(20)
287
(24)
328
(26)
369
(26)
272
(27)
311
(29)
350
(30)
259
(25)
297
(27)
334
(27)
250
(27)
289
(27)
326
(28)
240
(29)
277
(29)
316
(29)
1750
Liquid
pressure
(subcool)
299
(15)
339
(14)
378
(14)
282
(20)
320
(18)
363
(20)
274
(23)
313
(25)
353
(25)
262
(26)
299
(28)
338
(29)
247
(24)
285
(25)
323
(26)
239
(25)
276
(25)
314
(26)
230
(28)
267
(28)
306
(28)
2000
Liquid
pressure
(subcool)
280
(15)
319
(13)
358
(12)
267
(19)
307
(18)
346
(18)
262
(21)
299
(22)
337
(22)
251
(24)
288
(25)
326
(25)
237
(22)
274
(24)
312
(25)
230
(24)
266
(24)
303
(25)
222
(25)
259
(26)
296
(26)
-
Suction
pressure
113 115 117 93 94 95 81 81 81 67 67 66 51 51 51 43 43 44 35 36 37
Electrical connections
General information and grounding
The control box cover is held in place with three screws,
one screw in each lower corner and one screw at the top
center post. The control box can swing open by removing
the screw from the center of each side of the control box
and allowing the control box to lower an inch or so into a
pivotal position.
R-410A Outdoor Split-System Heat Pump Installation Manual - YH2E / THE2 / RHP143 Series 27
Johnson Controls Ducted Systems