Installation, Operation and Maintenance Manual
Occupancy
Determination
Flow Setpoint
29 46 66 89 117 148 182 262 357 466 267 891
Sequence Dependent Parameters
The following section shows factory programming for SE-ZEC Controller parameters that are control sequence specific.
Table 7: Factory Programmed Sequence Specific Parameters
Control Code 6101, 7101
6103, 7103 6104, 7104
6107, 7107 6109, 7109
Heating Type Cooling Only Staged Staged Staged SCR Incremental Staged
FAN-TYPE None None None None None None None
Number of Heating
Stages
No Heat 1 2 3 No Stages No Stages No Heat
Damper Polarity Normal Normal Normal Normal Normal Normal Normal
Supplemental
Heating Installed
FALSE FALSE FALSE FALSE FALSE FALSE TRUE
Box Heating Installed FALSE TRUE TRUE TRUE TRUE TRUE FALSE
Box Heating Stroke
Time
N/A N/A N/A N/A N/A 60 N/A
Box Heating Polarity N/A N/A N/A N/A N/A Normal N/A
Staged Device Min
Flow
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
N/A
Per Size
Table
Occupancy
Determination Flow
Setpoint
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
Per Size
Table
Occupancy Polarity N/A N/A N/A N/A N/A N/A N/A
Occupancy Sensor
Enable
FALSE FALSE FALSE FALSE FALSE FALSE FALSE
Standalone Mode TRUE,FALSE
TRUE,FALSE
TRUE,FALSE
TRUE,FALSE TRUE,FALSE
TRUE,FALSE
TRUE,FALSE
TRUE,FALSE TRUE,FALSE
Control Code 6201, 7201
6203, 7203 6204, 7204
6207, 7207 6209, 7209
Heating Type Cooling Only Staged Staged Staged SCR Incremental Staged