TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin 15
Temporary Occupancy Time
3
MSV 62 1 = 0 Hours
2=1Hour
3=2Hours
4=3Hours
5=4Hours
6=5Hours
7=6Hours
8=7Hours
9=8Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
14 = 13 Hours
15 = 14 Hours
16 = 15 Hours
17 = 16 Hours
18 = 17 Hours
19 = 18 Hours
20 = 19 Hours
21 = 20 Hours
22 = 21 Hours
23 = 22 Hours
24 = 23 Hours
25 = 24 Hours
Deadband
3
AV 63 2F°/1C° to
5F°/3C°
Reheat Time Base (BO5)
3
BV 64 0 = 15 Minutes
1 = 10 Seconds
Proportional Band MSV 65 1 = 3 (3°F/1.7°C)
2 = 4 (4°F/2.2°C)
3 = 5 (5°F/2.8°C)
4 = 6 (6°F/3.3°C)
5 = 7 (7°F/3.9°C)
6 = 8 (8°F/4.4°C)
7 = 9 (9°F/5.0°C)
8 = 10 (10°F/5.6°C)
Auto Fan BV 66 0 = Auto Speed
1 = Auto Speed/Auto Demand
Stand-by Time
3
AV 67 0.5 to 24.0 Hours
Unoccupied Time
3
AV 68 0.0 to 24.0 Hours
RH Display
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
BV 70 0 = Disabled
1 = Enabled
RH Setpoint
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
AV 71 30 to 100% RH
Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects
(Part 5 of 7)
Point Name Thermostat Point
(Type/Address)
Range