TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin46
Unoccupied Cool Setpoint AV 44 54.0°F/12.0°C to
100.0°F/37.5°C
BI 1 Configuration MSV 46 1 = None
2 = Rem NSB
3 = Motion N.O.
4 = Motion N.C.
5 = Window
BI 2 Configuration MSV 47 1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
Menu Scroll BV 49 0 = No Scroll
1 = Scroll Enabled
Auto Mode Enable BV 50 0 = Disabled
1 = Enabled
Temperature Scale BV 51 0 = °C
1 = °F
Pipe Number MSV 52 1 = 2-Pipe
2 = 4-Pipe
Password Value AV 56 0 to 1000
Fan Mode Sequence MSV 57 1 = Low- Medium - High
2 = Low - High
3 = Low - Medium - High - Auto
4 = Low - High - Auto
5 = On - Auto
Heating Setpoint Limit AV 58 40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit AV 59 54.0°F/12.0°C to
100.0°F/37.5°C
Setpoint Type BV 60 0 = Permanent
1 = Temporary
Setpoint Function BV 61 0 = Dual Setpoints
1= Attached Setpoints
Table 11: TEC26xx-0+PIR (Part 3 of 5)
Point Name Thermostat Point
(Type/Address)
Range