TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin 47
Temporary Occupancy Time MSV 62 1 = 0 Hour
2 = 1 Hour
3 = 2 Hours
4 = 3 Hours
5 = 4 Hours
6 = 5 Hours
7 = 6 Hours
8 = 7 Hours
9 = 8 Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
14 = 13 Hours
15 = 14 Hours
16 = 15 Hours
17 = 16 Hours
18 = 17 Hours
19 = 18 Hours
20 = 19 Hours
21 = 20 Hours
22 = 21 Hours
23 = 22 Hours
24 = 23 Hours
25 = 24 Hours
Deadband AV 63 2°F/1°C to
5°F/2.5°C
Proportional Band MSV 65 1 = 3 (3°F/1.2°C)
2 = 4 (4°F/1.7°C)
3 = 5 (5°F/2.2°C)
4 = 6 (6°F/2.8°C)
5 = 7 (7°F/3.3°C)
6 = 8 (8°F/3.9°C)
7 = 9 (9°F/5.0°C)
8 = 10 (10°F/5.6°C)
Auto Fan BV 66 0 = Auto Speed
1 = Auto Speed / Auto Demand
Stand-by Time AV 67 0.5 Hours to 24 Hours
Unoccupied Time AV 68 0.0 Hours to 24 Hours
Relative Humidity (RH) Display BV 70 0 = Disabled
1 = Enabled
RH Setpoint AV 71 30 to 95%
Dehumidification Hysteresis AV 72 2 to 20%
Dehumidification Max Cooling AV 73 20 to 100%
RUI 1 Configuration MSV 82 0 = None
1 = Filter
2 = Service
3 = COC/NH
4 = COC/NC
5 = COS
RBI 2 Configuration MSV 83 0 = None
1 = Filter
2 = Service
Table 11: TEC26xx-0+PIR (Part 4 of 5)
Point Name Thermostat Point
(Type/Address)
Range