Table 9: ZY04 to 12 Standard Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 42.2 45 50 45 246 44.4 45 50 47 256
11725 12 1 33.3 50.4 60 60 46 246 53.1 60 60 49 256
12525 18.6 1 51.6 73.3 80 80 67 246 76 80 80 70 256
13225 24 1 66.6 92 100 100 85 246 94.8 100 100 87 256
208-3-60 13.6 83.1 21 13.6 83.1 21 2.3 7 1.1
14225 31.8 2 88.3 119.1 125 125 110 246 121.9 125 125 112 256
None - - - 42.4 45 50 45 248 44.4 45 50 47 243
11725 16 1 38.5 57.1 60 60 53 248 59.6 60 60 55 243
12525 24.8 1 59.7 83.6 90 90 77 248 86.1 90 90 79 243
13225 32 1 77 105.3 110 110 97 248 107.8 110 110 99 243
230-3-60 13.6 83.1 21 13.6 83.1 21 2.3 7.2 1
14225 42.4 2 102 136.5 150 150 126 248 139 150 150 128 243
None - - - 19.9 20 25 21 125 20.9 25 25 22 121
11746 16.5 1 19.8 29.3 30 30 27 125 30.5 35 35 28 121
12846 27.8 1 33.4 46.3 50 50 43 125 47.5 50 50 44 121
13346 33 1 39.7 54.1 60 60 50 125 55.4 60 60 51 121
460-3-60 6.1 41 10 6.1 41 10 1.3 3.6 0.5
14246 41.7 2 50.2 67.3 70 70 62 125 68.5 70 70 63 121
None - - - 14.2 15 15 15 93 15 15 15 16 90
11758 17 1 16.4 23.6 25 25 22 93 24.6 25 25 23 90
08 (7.5)
575-3-60 4.2 33 7 4.2 33 7 1.1 2.5 0.4
13458 34 1 32.7 44 45 45 40 93 45 45 45 41 90
None - - - 42.4 45 50 45 246 44.6 45 50 47 256
11725 12 1 33.3 50.4 60 60 46 246 53.1 60 60 49 256
12525 18.6 1 51.6 73.3 80 80 67 246 76 80 80 70 256
13225 24 1 66.6 92 100 100 85 246 94.8 100 100 87 256
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 7 1.1
14225 31.8 2 88.3 119.1 125 125 110 246 121.9 125 125 112 256
None - - - 42.6 45 50 45 248 44.6 45 50 47 243
11725 16 1 38.5 57.1 60 60 53 248 59.6 60 60 55 243
12525 24.8 1 59.7 83.6 90 90 77 248 86.1 90 90 79 243
13225 32 1 77 105.3 110 110 97 248 107.8 110 110 99 243
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 7.2 1
14225 42.4 2 102 136.5 150 150 126 248 139 150 150 128 243
None - - - 20.2 25 25 21 125 21.2 25 25 23 121
11746 16.5 1 19.8 29.3 30 30 27 125 30.5 35 35 28 121
12846 27.8 1 33.4 46.3 50 50 43 125 47.5 50 50 44 121
13346 33 1 39.7 54.1 60 60 50 125 55.4 60 60 51 121
460-3-60 6.2 41 10 6.2 41 10 1.3 3.6 0.5
14246 41.7 2 50.2 67.3 70 70 62 125 68.5 70 70 63 121
None - - - 15.5 20 20 16 93 16.3 20 20 17 90
11758 17 1 16.4 23.6 25 25 22 93 24.6 25 25 23 90
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 2.5 0.4
13458 34 1 32.7 44 45 45 40 93 45 45 45 41 90
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 33
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals