HANDBOOK_75
If we click on COUNTERS, the following screen will
open, showing all counters. To see values, click on
READ.
Short explanaon of each COUNTER:
Version: Soware version of the PCB CONTROL part.
Opons: Parameter for internal use only.
Operaons: Number of mes the cam steps on
the OPEN or CLOSE micro switch.
Limitaons: Number of mes the limiter funcon
has been acvated, due to a higher torque than
the allowed.
End Order: Parameter for internal use only.
Time Error: Number of mes the motor has been stopped, as the TIEMPO DE MANIOBRA parameter value has been
overpassed, but the actuator has not reached either the OPEN or CLOSE posion yet. It usually happens when the
declutching lever is in MAN posion. (The user wants to move the actuator manually)
Power On: Number of mes the actuator remains without Power Supply.
BSR: Number of mes the actuator has been acvated by using the BSR system, due to a Power Supply failure. This
counter won’t work if the BSR system has not been installed on the actuator before.
To go back to the MENU, click on MAIN MENU.
This configuraon is possible only if our Posioner
(DPS) has already been installed in the actuator.
Click on DPS PARAM, the following screen will open
and allow you to set up the Banda Prop parameter.
The Banda Prop parameter should be 32 in all our
standard models.
Only in case of a S20 or B20 model with a 5 Sec./90º
working me, the Banda Prop value should change
into 55. Otherwise, the posioner (DPS) could not
work in a proper way.
Click on READ, to see the recorded value.
Select 32 or 55 and record the selected value.
To go back to the HOME MENU, click on MAIN MENU.