The actuator moves and then stops. The operang LED flashes red or green (see status LED).
»» High torque on the valve due to not removed end stops or solids in the valve. Valve must be checked!
»» Model size of the actuator is too small.
The actuator is in posion „open“ but the valve is closed or half opened.
»» Actuator is mounted on the valve with a wrong angle. Dismount, turn the actuator in manual mode to
correct angle, mount it.
The limit switches for end posion feedback do not work.
»» Check the wiring. Check the adjustment of the cams so that they trigger shortly before reaching the end
posion.
»» In load-free interrogaon of the limit switch, soot is formed inside. Actuator with gold contact switches
are to be used.
The actuator moves, but the valve does not.
»» The connecon between actuator and valve is damaged or incorrectly dimensioned.
For other malfuncons, please contact our technical service department.