3 Operation - Configuration - Parameterization
16
3.2.2 Controller (Cntr)
The actual value is provided for the controller by the analog input.
ConF -> Cntr ->
Parameters Value Description
Measured value
offset
OFFS
-1999 ...
0 ...
+9999
The measured value is corrected through this value (offset),
prior to being used as a controller input value and in the analog
selector.
Display start
SCL
-1999 ...
0 ...
+9999
On transducers with standard signal, a display value is
assigned to the physical signal.
Example: 0 to 20 mA = 0 to 1500 °C
Display end
SCH
-1999 ...
100 ...
+9999
Filter time constant
dF
0.0 ...
0.6 ...
100.0 (s)
Adaptation of the digital input filter (0 = Filter OFF)
Temperature unit
Unit
1 deg. Celsius
2 deg. Fahrenheit
(Setup program: Adjustable resistance of the KTY at 25 °C.)
Parameters Value Description
Controller type
CtyP
1 2-state controller
2 3-state controller
3 Continuous controller
Action
CACt
0 Direct: (The output level of the controller is > 0 when the actual
value exceeds the setpoint, e.g. cooling).
1 Inverse: (The output level of the controller is > 0 when the
actual value is smaller than the setpoint, e.g. heating.)
Output value,
manual mode
HAnd
-100 ...
0 ...
+101
Output level after switching to manual mode
101 = last output value
Output level at
Out-of-Range
rOut
-100 ...
0 ...
+100
Output level in the event of overrange or underrange
Setpoint limit start
SPL
-1999 ...
+9999
The setpoint limitation prevents the entry of values exceeding
the default range.
The setpoint limits are not effective when entering setpoints
via the interface. The correction value is limited for external
setpoints with offset.
Setpoint limit end
SPH
-1999 ...
+9999
(Setup program: Manual mode and self-optimization can be inhibited.)