• The recommended maximum ambient temperature is 158° F (70° C). For safe operaon take into
consideraon the internal temperature within the rack.
• Note the hot surface warning label on the top rear of the chassis.
Compliance Statements for Data Center
• The equipment is suitable for installaon as part of the Common Bonding Network (CBN).
• The equipment is suitable for installaon in locaons where the Naonal Electrical Code (NEC)
applies.
• The baery return connecon is to be treated as an isolated DC return (that is, DC-I), as dened in
GR-1089-CORE.
• You must provision a readily accessible device outside of the equipment to disconnect power. The
device must also be rated based on local electrical code pracce.
Compliance Statements for EMC Requirements