Select from the following rack options:
Two-post rack—a freestanding enclosed cabinet with two mounting posts in the front
Telco-type rack—two adjacent mounting posts that you must secure to the floor or an overhead
structure
Four-post rack—a freestanding open rack, either open or closed
The rack must have at least two mounting posts.
The distance between the mounting holes in the two posts must be 18.31 in. +/-.063 in., as specified in
the EIA-310-D document.
An optional mounting kit is available for midchassis mounting. Contact your Juniper Networks sales
representative for more information.
RELATED DOCUMENTATION
CTP150 Rack Requirements | 23
CTP150 Space Requirements | 24
CTP150 Rack Installation | 24
CTP150 Space Requirements
If you use an enclosed rack for the device, ensure that there is a minimum of 3 in. of clearance between
the inner side wall and the system. This clearance space ensures adequate air flow.
RELATED DOCUMENTATION
CTP150 Rack Requirements | 23
CTP150 Mechanical Requirements | 23
CTP150 Rack Installation | 24
CTP150 Rack Installation
To confirm proper equipment rack installation, verify the following:
Racks are installed and electrically grounded according to manufacturer instructions.
24

Table of Contents

Other manuals for Juniper CTP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper CTP Series and is the answer not in the manual?

Juniper CTP Series Specifications

General IconGeneral
BrandJuniper
ModelCTP Series
CategoryServer
LanguageEnglish

Related product manuals