Table 62: Typical Power Consumpon for the EX4400 Switch Models
(Connued)
Model Typical Power Consumpon
EX4400-48T 102.7 W
EX4400-48F 128.6 W
EX4400 DC Power Cable Specicaon
EX4400 DC power supplies require a D-Sub 3W3- type connector. The three pins on the connector
provide –48 VDC input (–), return (+), and ground connecons to the power supply.
NOTE: Regardless which DC power cable you use, you must connect the EX4400 to earth
ground before you connect it to power.
DC power cables, each 4 m (approximately 13.1 ) long, are supplied with the EX4400 switches. The
provided cables include the three-pin connector on one end and three insulated wires at the opposite
end, for connecon to the site’s DC power distribuon system.
"EX4400 DC Power Cable Specicaon" on page 109 lists the specicaons for the EX4400 DC power
cables.
Table 63: EX4400 DC Power Cable
Specicaons
Juniper Model Wire Funcon Insulaon Color Wire Size
CBL-JNP-PWR-DSUB
(straight cable)
–48 VDC input (–) Blue 8 AWG (8.4 mm²), 90° C
Return (+) Black 8 AWG (8.4 mm²), 90° C
Ground Green and yellow 8 AWG (8.4 mm²), 90° C
CBL-JNP-PWR-DSUB4
(straight cable)
–48 VDC input (–) Blue 12 AWG (8.4 mm²), 90°
Return (+) Black 12 AWG (8.4 mm²), 90°
109