Figure 111: Proper Load Balancing for JNP10K-PWR-AC2 Power Cables on MX100016
g100688
OR
12. For each power cable, insert the end of the cable with the Anderson connector into the
JNP10K-PWR-AC2 power supply module. The connector snaps and locks the cable into position.
WARNING: Ensure that the power cords do not block access to router components
or drape where people can trip on them.
13. If the AC or DC power source outlets have a power switch, set them to the on (|) position.
14. Set the three dip switches to set the inputs and whether the power supply is running at 3000 W,
5000 W, or 5500 W. See Table 57 on page 215.
Set both enable switches to the on position when using both source inputs. When not using source
redundancy, set the unused source to the O (off) position. The LED turns red and indicates an error if
a source input is not in use and the enable switch is | (on).