1. Attach the electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
the ESD point on the chassis. There is an ESD point located next to the protective earthing terminal
and below PSU 5 on the PTX10008 rear panel (see Figure 132 on page 271) and below PSU_9 on the
PTX10016 (see Figure 133 on page 271).
Figure 132: ESD Point on PTX10008 Chassis Rear
1ESD point
Figure 133: ESD Point on PTX10016 Chassis Rear
1ESD point
2. Flip the Enable switch next to the appliance inlet on the power supply to the standby position.
3. Disconnect power from the router by performing one of the two following tasks:
If the AC power source outlets have a power switch, set them to the off (O) position.
If the AC power source outlets do not have a power switch, gently pull the male end of the power
cords connected to the power source outlets out of the outlets.