Figure 185: Proper Load Balancing for JNP10K-PWR-DC2 Power Cables on PTX100016
g100690
WARNING: Ensure that the power cords do not block access to router components
or drape where people can trip on them.
18. Set the three dip switches to set the inputs and whether the power supply is running at 3000 W,
5000 W, or 5500 W. See Table 80 on page 319 and Figure 186 on page 320.
Set both enable switches to the on position when using both source inputs. When not using source
redundancy, set the unused source to the off (O) position. The LED turns red and indicates an error if
a source input is not in use and the enable switch is on (|).
Table 80: Setting the JNP10K-PWR-DC2 Dip Switches
FieldStateSwitch
IP0 is presentOn1
IP0 is not presentOff
IP1 is presentOn2
IP1 is not presentOff
319