EasyManua.ls Logo

Kamstrup flowIQ - Connecting Pulse and Analog Inputs

Kamstrup flowIQ
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Kamstrup A/S • 55122714_A2_GB_04_2021
flowIQ® Gateway
6.4.2 Connecting pulse meters
Some modules are equipped with two pulse inputs, In-A and In-B, to collect and accumulate
pulses. The pulse inputs are physically placed on the module. However, the accumulation and
logging are performed by flowIQ® Gateway. Depending on where the communication module is
placed (slot 1 or slot 2), the pulse inputs will be registered as In-A1 and In-B1 or In-A2 and In-B2.
Thus, you can install two communication modules with two pulse inputs each and connect up
to four pulse meters to flowIQ® Gateway. For examples, see section 10 "Communication module
combinations and examples".
Here is an example of the module HC-003-32: linkIQ®/wM-Bus module:
Upon delivery, the configurations of pulse inputs A and B can be changed with METERTOOL HCW.
The preset value of In-A1 and In-B1 can be set via the front keys, see section 7 "Field deployment –
Configuration".
6.4.3 Connecting Analog input 4…20 mA devices
Module HC-003-41 is equipped with Analog 2 x 4…20 mA inputs. The module writes the values of
the analog signals to the P1 and P2 registers of flowIQ® Gateway. The inputs are physically placed
on the module. However, the accumulation and logging are performed by flowIQ® Gateway. Only
one analog input module is supported in flowIQ® Gateway.
Pulse inputs
Terminal 65: Pulse In-A (+)
Terminal 66: Pulse In-A (-)
Terminal 67: Pulse In-B (+)
Terminal 68: Pulse In-B (-)
Antenna
Terminals
Max cable size 1.5 mm²
External power
Terminal 98: 24 VAC/VDC
Terminal 97: 24 VAC/VDC
Analog inputs
Terminal 60: + supply In 1, In 2
Terminal 58: Signal In 1
Terminal 59: Signal In 2
Terminal 57: - supply In 1, In 2

Table of Contents

Related product manuals