EasyManua.ls Logo

Kamstrup flowIQ - Communication Module Combinations; Configuration Examples

Kamstrup flowIQ
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34 Kamstrup A/S • 55122714_A2_GB_04_2021
flowIQ® Gateway
10 Communication module combinations and examples
Depending on the chosen communication modules installed in module slots 1 and 2, up to 5
meters can be connected and data forwarded from flowIQ® Gateway:
Example 1
Primary connection terminals Module slot 1 Module slot 2
1 x flowIQ® 2200/3200 meter
(serial V1 connection)
3 x Pt500 temperature
sensors
HC-003-67
1 x Modbus RTU, 2 pulse inputs
(In-A, In-B)
HC-003-20/21/22
1 x M-Bus module, 2 pulse inputs
(In-A, In-B)
In example 1, the primary module is connected to 1 x flowIQ® 2200/3200 meter and up to 3 x
Pt500 temperature sensors.
Module slot 1 has a Modbus output with 2 pulse inputs, In-A1 and In-B1.
Module slot 2 has an M-Bus module with 2 pulse inputs, In-A2 and In-B2.
Only V1 data is available on pulse input.
For further information, see the module data sheet.
Example 2
Primary connection terminals Module slot 1 Module slot 2
1 x flowIQ® 2200/3200 meter
(serial V1 connection)
3 x Pt500 temperature
sensors
HC-003-60
1 x LON TP/FT-10, pulse inputs
(In-A, In-B)
HC-003-20/21/22
1 x M-Bus module, 2 pulse inputs
(In-A, In-B)
In example 2, the primary module is connected to 1 x flowIQ® 2200/3200 meter and up to 3 x
Pt500 temperature sensors.
Module slot 1 has a LON output with 2 pulse inputs, In-A1 and In-B1.
Module slot 2 has an M-Bus module with 2 pulse inputs, In-A2 and In-B2.
Only V1 data is available on pulse input.
For further information, see the module data sheet.

Table of Contents

Related product manuals