9Kamstrup A/S • 55122714_A2_GB_04_2021
flowIQ® Gateway
3.5 Communication
If used with a radio module, the device must be installed to provide a separation
distance of minimum 20 cm from all persons.
Must NOT be co-located in conjunction with any other antenna or transmitter.
Communication module 2 plug-in slots
Antenna External/internal depending on communication module
Optical interface Configuration interface
3.6 Input
flowIQ® 2200/3200 meter Proprietary Kamstrup communication
Cable (ordered separately) 1.5 m 5000491
7.5 m (can be shortened) 5000493
Temperature sensors 3 x Pt500
3.7 Connections and inputs
3.7.1 Primary connection terminals
The primary connection terminals are reserved for connection of a flowIQ® 2200/3200 meter and
3 Pt500 temperature sensors.
Description Schematic Overview
The flowIQ® 2200/3200
meter cable is connected
in the following way:
Black à minus (-) input 11
Red à plus (+) input 9
Green à V1 input 10
The 3 Pt500 temperature
sensors are connected to
terminals t1…3
t2
t3
V1
V2
t1
+
-
-
+
-
+