MULTICAL® 403
3.2 Flow sensor position
A Recommended flow sensor posiion.
B Recommended flow sensor posiion.
C Unccepble posiion due o risk of ir
build-up.
D Accepble posiion in closed sysems.
E A flow sensor ough no o be plced
immediely fer  vlve, wih he
excepion of block vlves (bll vlve ype)
which mus be fully open when no used for
blocking.
F A flow sensor mus never be plced on he
inle side of  pump.
G A flow sensor ough no o be plced fer
double bend in wo plnes.
E
F
G
B
C
D
A
In order o void cviion, he bck pressure  he flow sensor (he pressure  he flow sensor
oule) mus be minimum 1.5 br  q
p
(nominl flow) nd minimum 2.5 br  q
s
(mximum flow).
This pplies o emperures up o pprox. 80 °C.
The flow sensor mus no be exposed o lower pressure hn mbien pressure (vcuum).

Other manuals for Kamstrup MULTICAL 403

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 403 and is the answer not in the manual?

Kamstrup MULTICAL 403 Specifications

General IconGeneral
TypeUltrasonic Heat Meter
Flow SensorUltrasonic
Pressure RatingPN16
Battery LifeUp to 16 years
ApprovalMID Class 2
DisplayLCD
CommunicationM-Bus, Wireless M-Bus, Modbus, BACnet
Power SupplyBattery
AccuracyClass 2
Protection ClassIP54
Housing MaterialComposite
Flow Rate Range0.6 m3/h to 15 m3/h

Related product manuals