Installation and Connection
Plug in all connectors only in off-circuit condition !
Observe correct phase sequence of the motor!
Shielded motor line
PTC-Connector*
)
PTC-Connector*
)
Brake +
Brake –
Motor
Power connector
A
B
C
D
1
2
3
4
PE
U
V
W
ext. brake supply unit
with own voltage supply
(optionally)
Apply shieldings over a large
contact surface of the mounting
plate
gr/ye
1
2
3
7
8
5
6
Motor connector
3.3.5 Connection of the temperature monitoring
T1
K1
12 11
T2
Motor-PTC
Other
Terminals T1, T2
Tripping resistance 1.65...4 kOhm
Reset resistance 0.75...1.65 kOhm
Design in accordance with VDE 0660 Part 302
This function can be activated by the machine builder by software
Do not lay connecting cable together with control cable
Permissible in the motor cable only with double shielding
Connect relay K1 for fire prevention in regenerative operation (see 3.3.6)