How to... 3
Man-1452EN Rev.02
Sigma ZXT Operation Manual
12
Disable Relay Outputs
Allows disabling of panel relay outputs, during periods of maintenance or testing to prevent unwanted signalling.
1. Enter USER MENU (Access Level 2) using passcode or Enable key-switch.
2. Select ENABLE/DISABLE menu option.
3. Select RELAYS menu option.
4. Use up/down cursor keys to select the relay output to disable.
5. Use left/right cursor key to change setting to DISABLED.
6. General Disablement LED will illuminate.
To enable relay outputs return to menu setting and toggle setting back to ENABLED.
Warning!! Disablement of relay outputs will prevent any remote signalling or activation of remote equip-
ment.
Disable Sounder Outputs
Allows disabling of sounder outputs, during periods of maintenance or testing to prevent unwanted activations.
1. Enter USER MENU (Access Level 2) using passcode or Enable key-switch.
2. Select ENABLE/DISABLE menu option.
3. Select SOUNDERS menu option.
4. Use up/down cursor keys to select DISABLE ALL or select a specific sounder from the list.
Note: DISABLE AL will disable only sounder outputs listed on the LCD.
5. Use left/right cursor key to toggle setting of the selected option.
6. General Disablement and Sounder Disable LED will illuminate.
To enable sounder outputs return to menu setting and toggle setting back to enabled state.
Warning!! Disablement of sounder outputs will prevent any notification of alarms to personnel within the
risk area.
Disable Monitored Inputs
Allows disabling of monitored outputs, during periods of maintenance or testing to prevent unwanted activations.
1. Enter USER MENU (Access Level 2) using passcode or Enable key-switch.
2. Select ENABLE/DISABLE menu option.
3. Select MONITORED INPUTS menu option.
4. Use up/down cursor keys to highlight the input to disable.
5. Use left/right cursor key to change setting to DISABLED.
6. General Disablement and Flooding Zone Fault/Disabled LED will illuminate.
To enable monitored inputs return to menu setting and toggle setting back to ENABLED.
Warning!! Disablement of monitored inputs will prevent the inputs from being activated, any functions as-
sociated with the input will not operate.
Disable Panel Inputs
Allows disabling of non-monitored panel inputs, during periods of maintenance or testing to prevent unwanted sig-
nalling.
1. Enter USER MENU (Access Level 2) using passcode or Enable key-switch.
2. Select ENABLE/DISABLE menu option.
3. Select PANEL INPUTS menu option.
4. Use up/down cursor keys to select the input to disable.
5. Use left/right cursor key to change setting to DISABLED.
6. General Disablement and any other associated Disablement LEDs will illuminate.
To enable panel inputs return to menu setting and toggle setting back to ENABLED.
Warning!! Disablement of relay outputs will prevent any remote signalling or activation of remote equip-
ment.