How to... 3
Man-1452EN Rev.02
Sigma ZXT Operation Manual
13
Enable Sounder Delay
Function allows the option to delay or not delay activation of 1
st
Stage Sounder Outputs S1 and S2 when an alarm
is activated on the Panel. The delay period must be programmed in the ENGINEERING MENU (Access Level 3) by
a qualified engineer.
1. Enter USER MENU (Access level 2) using passcode or Enable key-switch.
2. Select SOUNDER DELAY menu option.
3. Use up/down cursor keys to highlight sounder output.
4. Use left/right keys to select between IMMEDIATE and DELAYED.
Immediate –When an alarm occurs on the panel sounder outputs will operateimmediately.
Delayed - When an alarm occurs on the panel a pre-determined delay period will pass before sounder outputs operate.