ES749 Flow Computer
49
FLUID DATA
6.7
FLUID DATA
Select the uid. There are three types:
1. Steam / Water
All information required for steam and water (such as saturated steam
curve, density and thermal capacity) is permanently stored in the ow
computer.
2. Fluid Displayed
Preset information for other uids (such as air and natural gas) is
stored in the ow computer and can directly adopted by the user.
If the preset values need to be changed to t your specic process
conditions, then proceed as follows:
Select the uid (air or natural gas) and press the ENTER key (this
sets all of the preset values).
Re-select the submenu group "FLUID TYPE", now choose
"GENERIC" and ENTER. Now the preset values for the previously
selected uid can be altered.
3. Generic Fluid
Select the setting "GENERIC" for the Fluid type submenu. The
characteristics of any uid can now be dened by the user.
Selection:
GENERIC, WATER, SATURATED STEAM, SUPERHEATED
STEAM, DRY AIR, HUMID AIR, HUMID GAS, NATURAL
GAS, NATURAL GAS (NX-19), HYDROGEN, ARGON,
METHANE, NITROGEN, CARBON DIOXIDE, PROPANE,
OXYGEN, ETHANE, HELIUM
Display: GENERIC
FLUID TYPE
Select the density for a generic uid at reference temperature and
pressure (see "STP REFERENCE" in "OTHER INPUT" submenu
group).
Input:
Number with oating decimal point: 0.0001...10000.0
Display: .0760 #/ft3
REF. DENSITY
FLUID TYPE
REF. DENSITY