ES749 Flow Computer
72
6.11
CURRENT
OUTPUT
CURRENT OUTPUT
Select the current output to be congured. The ow computer offers
two current outputs.
Selection:
1 (Current output 1)
2 (Current output 2)
Display: 1
SELECT OUTPUT
Assign a variable to the current output.
Selection:
HEAT FLOW, MASS FLOW,
COR. VOLUME FLOW, VOLUME FLOW,
TEMPERATURE, TEMPERATURE 2,
DELTA TEMPERATURE, PRESSURE, DENSITY, PEAK
DEMAND, DEMAND LAST HOUR
Display: VOLUME FLOW
ASSIGN CURRENT OUT.
Dene the 0 or 4 mA low scale current value. The current for the
scaled full scale value is always 20 mA.
Selection:
0-20 mA, 4-20 mA, NOT USED
Display: 4-20 mA
CURRENT RANGE
Set the low scale value to the 0 or 4 mA current signal for the
variable assigned to the current output.
Input:
Number with oating decimal point: -999999...+999999
Display: .000 ft3/h
LOW SCALE VALUE
Set the full scale value to the 20 mA current signal for the variable
assigned to the current output.
Input:
Number with oating decimal point:
-999999...+999999
Display: 1000.00 ft3/h
FULL SCALE VALUE
SELECT OUTPUT
ASSIGN CURRENT
OUT
CURRENT RANGE
LOW SCALE
FULL SCALE