ES749 Flow Computer
32
EZ SETUP
EZ SETUP
EZ Setup
Example:
Steam Mass
Vortex Flowmeter
UNITS
FLOW EQUATION
The EZ Setup routine is a quick and easy way to congure the
most commonly used instrument functions. We recommend rst
completing the EZ Setup routine for the ow equation and meter
type for your initial application. The setup can then be customized
using the complete submenu groups described later in this chapter.
Caution:
Entering the EZ Setup mode automatically sets many
features to a default value (without prompting the user).
This may cause any previously programmed information to
be lost or reset.
Selection:
YES, NO
Display: EZ SETUP? YES
PAUSE COMPUTATIONS
Note:
The "Pause Computations" warning message informs the
user that all computations are halted while programming EZ
Setup.
Select the desired units of measure.
Selection:
METRIC, ENGLISH
Display: ENGLISH
UNITS?
Select the ow equation appropriate for your application.
Selection:
STEAM MASS, STEAM HEAT, STEAM NET HEAT, STEAM
DELTA HEAT, GAS CORRECTED VOLUME, GAS MASS,
GAS COMBUSTION HEAT, LIQ.CORRECTED VOLUME,
LIQUID MASS, LIQ. COMBUSTION HEAT, LIQUID
SENSIBLE HEAT, LIQUID DELTA HEAT,
STM – CONDENSATE HEAT
Display: STEAM MASS
FLOW EQUATION
6.2
EZ
SETUP