Start End Description Data type
8578 8578 Sum over lifetime: current loop, warning value exceeded
Warning
The following error numbers are counted: {127}
u 16bit
8579 8579 Sum over lifetime: current loop, sensor fault
Alert
The following error numbers are counted: {69}
u 16bit
8580 8580 Sum over lifetime: current loop, trip value exceeded
Alert
The following error numbers are counted: {68}
u 16bit
8581 8581 Sum over lifetime: current loop, trip value exceeded
Interlocked alert
The following error numbers are counted: {68}
u 16bit
8582 8582 Temperature sensor 1, temperature value
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8583 8583 Temperature sensor 1, trip value
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8584 8584 Temperature sensor 2, temperature value
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8585 8585 Temperature sensor 2, trip value
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8586 8586 Temperature sensor 1, ohmic value u 16bit
8587 8587 Temperature sensor 2, ohmic value u 16bit
8588 8588 Leakage monitoring 1, ohmic value u 16bit
8589 8589 Leakage monitoring 1, trip value u 16bit
8590 8590 Phase voltage L1 u 16bit
8591 8591 Phase voltage L2 u 16bit
8592 8592 Phase voltage L3 u 16bit
8594 8594 Current loop value u 16bit
8595 8595 Current loop trip value u 16bit
8596 8596 Leakage monitoring 2, ohmic value u 16bit
8597 8597 Leakage monitoring 2, trip value u 16bit
8598 8598 Sum over lifetime: motor temperature exceeded
Warning
The following error numbers are counted: {122}
u 16bit
8600 8600 Sum over lifetime: limit of frequency of starts
Warning
u 16bit
8601 8601 Sum over lifetime: limit of frequency of starts
Alert, interlocked
u 16bit
8602 8602 Module condition, phase undervoltage
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit