1 Supplementary Operating Manual
31 of 48
AmaControl
2301.83/04-EN
Start End Data type Description
10789 10789 Running time until service due, in hours u 16bit
10794 10794 Module condition, temperature 1
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10795 10795 Temperature sensor 1, resistance actual value 1...65,535Ω, 0 = not
applicable
u 16bit
10796 10796 Module condition, temperature 2
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10797 10797 Temperature sensor 2, resistance actual value1 - 65,535Ω, 0 = not
applicable
u 16bit
10798 10798 Module condition, leakage 1
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10799 10799 Leakage 1, resistance actual value1...65,535 Ω, 0 = not applicable u 16bit
10818 10818 Module condition, general monitoring
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10828 10828 Totalled operating time Operating time = value * 10 minutes
0...4,294,967,296minutes
Low word first
u 32bit
10854 10854 Temperature sensor 1, actual value
Temperature = (value - 32768) / 100-327.00°C…+327.00°C
65535 = not available
s 16offset
10855 10855 Temperature sensor 2, actual value
Temperature = (value - 32768) / 100-327.00°C…+327.00°C
65535 = not available
s 16offset