EN61000-6-1, EN61000-6-2, EN61000-6-3,
EN61000-6-4,EN61000-4-16, EN61000-4-18,
EN61000-4-29
Safety Regulation
Grid Regulation
EMC
IEC/EN 62109-1&2, IEC62040-1
AS/NZS 4777.2, VDE-AR-N4105, VDE0126-1-1
Display
Communication Interface
Euro Efficiency
MPPT Efficiency
Protection Function
RS485/CAN2.0/WIFI
94.0%
97.6%
97.0%
99.5%
LCD/APP
Short Circuit Protection, AC Leakage Fault Protection,
Grounding Fault Protection, Anti-islanding Protection,
Overload Protection、Surge Protection 、DC Polarity
Protection
Max. Conversion Efficiency
(From Battery)
Max. Conversion Efficiency
(From PV)
73
www.kstar.com
74
www.kstar.com
Table 9.1 Grid specification (single-phase)
Grid
Specification
Output Voltage
Range (Vac)
Output Frequency
Range (Hz)
Boot wait time(S)
China
187-252 48-50.5 30
Germany
184-264 47.5-51.5 60
Australia
180-260 47-52 60
Italy
184-276 49.7-50.3 60
Spain
196-253 48-50.5 180
U.K.
184-264 47-52 180
Hungary
196-253 49-51 300
Belgium
184-264 47.5-51.5 60
W-Australia
180-260 45-52 60
Greece
184-264 49.5-50.5 180
France
184-264 47.5-50.4 60
Bangkok
150-264 49-51 150
Thailand
150-264 48-51 60
Local
150-280 45-55 30
60Hz
184-264 59.5-60.5 60
User Manual User Manual
High Frequency Isolation
Natural Convection
Cooling
Topology
Certification& Standard