20
3. How to measure DAR/ PI
DAR and PI are automatically measured during a normal
continuousmeasurement of insulation resistances. Set the
Range switch to any desired range and measure the test
objectcontinuously.
-1minafterastartofcontinuousmeasurement:
LCDshowsDARvalue.
-10minafterastartofcontinuousmeasurement:
LCDshowsPIvalue.
WhenDAR/PIvaluesaredisplayedasno:
DAR and PI values are determined by Methods 1. and 2.
as described above, therefore, they are displayed as no
whenthemeasuredinsulationresistancesfallunderanyofthe
followingcases.
*1measuredvalueis0.0MΩ
*2measuredvalueisOL
*OLis displayed when the measured value exceeds
the upper limit of the measuring range at each insulation
resistancerange.
Range Upperlimit
250V 105.0MΩ
500V 1050MΩ
1000V 2.10GΩ
2500V 105.0GΩ
5000V 1200GΩ
www.calcert.com sales@calcert.com1.888.610.7664
0
5
10
15
20
25
30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KYORITSU KEW3125A and is the answer not in the manual?

KYORITSU KEW3125A Specifications

General IconGeneral
BrandKYORITSU
ModelKEW3125A
CategoryTest Equipment
LanguageEnglish

Related product manuals