Select the model of the installed electric lock.
OFF = FAIL SECURE or bistable model
ON = FAIL SAFE mode
If the operator is not equipped with an electric lock keep setting to OFF.
We recommend that you modify the default technical password.
To this purpose please refer to the “Password management” paragraph.
14.3) INITIAL SET-UP
From general programming menu, F1 button allows moving forward among menu symbols.
Select INITIAL SET-UP symbol.
Give a quick pulse to ENTER button to enter the “Initial setup” section.
Type the 10-character technical password for access to set-up configuration.
The default technical password supplied by Label to ET-DSEL digital programmer is “A-A-A-A-A-A-
A-A-A-A”
Press the button in correspondence with letter A, asterisk appears on the first letter case on the
display; repeat this operation for all the other characters required.
If the password typed is correct, you enter the section dedicated to set-up configuration; if the
password typed is wrong, you return to general programming menu.
In this section, F1 / F3 buttons allows selecting the function OFF / ON status, while
button allows moving to the following function.
Press F2 button to return to previous function.
Select the automation model:
ON = ETERNA 90
OFF = ETERNA 150/300T
If the ET-DSEL digital programmer is connected to two automatic doors, select by pressing the F3
button once whether the initial set-up concerns the operator of door 1, or that of door 2.
The initial set-up must be carried out separately on each operator.
OPERATOR 1
OPERATOR 2
Select ON only if a safety sensor has been installed on closing on input E.C.1.
BATTERY PACK
OFF = NOT PRESENT
ON = USED
If S02 function is set to OFF only
Only select ON if a double electric lock for chemist's function is installed in the operator.
Please refer to the "CHEMIST'S FUNCTION" paragraph.
If no chemist's electric lock is installed keep setting to OFF.
BEFORE STARTING THE SET-UP MOVE THE DOOR TO THE CLOSING POSITION.
THE AUTOMATION WILL DETECT AUTOMATICALLY THE CORRECT DIRECTION OF OPENNG DURING THE SET-UP CYCLE.
SET-UP FULL: mandatory for the first installation of the automation.
SET-UP PARTIAL: to repeat the learning of the leaves stroke in case the mechanical limit switch are moved,
without changing the previously set functions.
ATTENTION! The partial set-up does not work on a new automation at the first installation. In this case, if the
Partial option is selected, the buzzer of the electronic control unit will warn of the error by emitting a
continuous sound for 4 seconds.
Press the F1 button to select the "FULL" set-up.