EasyManuals Logo

LEGRAND Keor T Series User Manual

LEGRAND Keor T Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
36
CAUTION: Do not remove the communication cables between the UPSs during
parallel operation.
In case the communication cable is removed or damaged during parallel operation and the communication
is lost then the slave UPS which cannot communicate with the master UPS will disconnect from the output
bus and turn o. The other UPSs will continue normal operation. In such a case, this UPS should be turned
o completely in order to insert its communication cable again and then switched on again.
Start up for “PARALLEL UPSs not on Maintenance Bypass Mode;
1. Switch the auxiliary supply circuit breaker on the distribution panel to ON position.
2. Switch the mains supply circuit breaker on the distribution panel to ON position.
3. Switch Q4 (Auxiliary Supply) circuit breakers of all UPSs ON position.
4. Switch Q1 (Mains Supply) circuit breakers of all UPSs to ON position.
5. Switch Q6 (Inrush) circuit breakers of all UPSs to “ON” position.
6. Touch Battery icon to see Battery / DC menu measurement. Do not close the battery circuit breakers (F5)
until the dierence between DC bus and Battery voltages decreases below 10V.
7. If exists, switch external Battery circuit breaker to ON position.
8. Switch Q2 (Output) circuit breakers of all UPSs to ON position.
9. If exists, switch the output circuit breakers on the distribution panel to ON position (o unit output
switch and OS General Output switch).
Start up for “PARALLEL UPSs on Maintenance Bypass Mode;
1. Switch Q4 (Auxiliary Supply) circuit breakers of all UPSs ON position.
2. Switch Q1 (Mains Supply) circuit breakers of all UPSs to ON position.
3. Switch Q6 (Inrush) circuit breakers of all UPSs to ON position.
4. LCDs will be ON. See M. Bypass Mode written on LCD of all UPS.
5. Touch Battery icon to see Battery / DC menu measurement. Do not close the battery circuit breakers (F5)
until the dierence between DC bus and Battery voltages decreases below 10V.
6. If exists, switch external Battery circuit breakers to ON position.
7. Switch F5 (Battery) circuit breakers of all UPSs to ON position.
8. Switch Q2 (Output) circuit breakers of all UPSs to ON position.
9. If exists, switch the output circuit breakers on the distribution panel to “ON” position (o unit output switch
and OS General output switch).
10. Switch Q3 (Maintenance Bypass) circuit breakers of all UPSs to OFF position.
11. If exists, Switch Q ( External Maintenance Bypass) circuit breaker to OFF position.
12. See “Online Mode written on LCDs.
8.2. Procedure for Commissioning and Start-Up
If the UPSs are not factory parallel congured; the initially started-up UPS will operate as master and
the remaining UPS’s will operate as slave. According ID numbers dened for each UPS, Master and Slave
messages should be observed on the LCD panel. On the master unit, candidate master UPS is also shown
as CX.
CX represents the best available master candidate UPS among the slave UPSs. X represents the ID number
of this slave UPS. In case the master UPS fails, then this candidate assigned UPS becomes Master.
ID-1 Master / CX Online Mode
Menu

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LEGRAND Keor T Series and is the answer not in the manual?

LEGRAND Keor T Series Specifications

General IconGeneral
BrandLEGRAND
ModelKeor T Series
CategoryUPS
LanguageEnglish

Related product manuals