EasyManua.ls Logo

LEGRAND Keor T Series - 8.3. Procedure for Decommissioning

LEGRAND Keor T Series
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
KEOR T
Operating Manual
CAUTION: Do not try to insert its communication cable while it is operating.
The Redundancy System expects to have at least one more UPS than N value. Otherwise
it shall provide Redundancy Lost alarm. The same alarm shall also appear in case:
Load % > N / ( N+1 ) * 100
8.3. Procedure for Decommissioning
Decommissioning “PARALLEL UPS without switching to Maintenance Bypass Mode;
1. If exists, switch the output circuit breakers on the distribution panel to OFF position (o unit output switch
and OS General Output switch).
2. Switch Q2 (Output) circuit breakers of all Slave to “OFF position.
3. Switch Q2 (Output) circuit breaker of Master toOFF position.
4. Switch F5 (Battery) circuit breakers of all Slave to “OFF position.
5. If exists, switch external Battery circuit breakers of all Slave to “OFF position.
6. Switch F5 (Battery) circuit breaker of Master to “OFF position.
7. If exists, switch external Battery circuit breaker of Master toOFF position.
8. Switch Q6 (Inrush) circuit breakers of all Slave to “OFF position.
9. Switch Q6 (Inrush) circuit breaker of Master to “OFF position.
10. Switch Q1 (Mains Supply) circuit breakers of all Slave to “OFF position.
11. Switch Q4 (Auxiliary Supply) circuit breakers of all Slave to “OFF position.
12. Switch Q1 (Mains Supply) circuit breaker of Master to “OFF position.
13. Switch Q4 (Auxiliary Supply) circuit breaker of Master to “OFF position.
Decommissioning “PARALLEL UPS with switching Maintenance Bypass Mode;
1. Go to Commands menu of Master UPS, enter User password (1111).
2. In page Priority, select Bypass Mode, save and conrm, go back to Energy Flow Diagram screen.
3. Check that UPS is in Bypass Mode operation. See all UPSs switch to Bypass Operation.
4. If exists , Switch Q (External Maintenance Bypass) circuit breaker to ON position and keep internal
Maintenance Bypass Q3 circuit breakers of all units to OFF position.
5. If External Maintenance Bypass Q is not present , then Switch Q3 (Maintenance Bypass) circuit breakers of
all Slave to “ON position , then Switch Q3 (Maintenance Bypass) circuit breaker of Master to “ON position.
6. If exists, switch the output circuit breakers on the distribution panel to OFF position (o unit output switch
and OS General Output switch).
7. Switch Q2 (Output) circuit breakers of all Slave to “OFF position.
8. Switch Q2 (Output) circuit breaker of Master toOFF position.
9. Switch F5 (Battery) circuit breakers of all Slave to “OFF position.
10. If exists, switch external Battery circuit breakers of all Slave to “OFF position.
11. Switch F5 (Battery) circuit breaker of Master to “OFF position.
12. If exists, switch external Battery circuit breaker of Master toOFF position.
13. Switch Q6 (Inrush) circuit breakers of all Slave to “OFF position.
14. Switch Q6 (Inrush) circuit breaker of Master to “OFF position.
15. Switch Q1 (Mains Supply) circuit breakers of all Slave to “OFF position.
16. Switch Q4 (Auxiliary Supply) circuit breakers of all Slave to “OFF position.
17. Switch Q1 (Mains Supply) circuit breaker of Master to “OFF position.
18. Switch Q4 (Auxiliary Supply) circuit breaker of Master to “OFF position.

Table of Contents

Related product manuals