* Keor T 60kVA battery fuses are xed.
7. Operating Procedures For Single Systems
7.1. Preparations
UPS is shipped with 3pcs of battery fast fuses in a plastic package attached to the front side of UPS.
After all connections are completed as described in Keor T Installation Manual, the battery fuses must be placed
as shown below. The fuses indicators should be placed at top. Use only the fuses delivered with the UPS.
Figure.7.1-1
Figure.7.1-2
KEOR T 5-30KVA
KEOR T 40-50KVA
INDICATORS