CLIMATIC™50 – IOM – Rooftops/ Aircoolair CL50-ROOFTOPS-IOM-1107-E
11
For each time zone, the set following set points following can be modified:
LIST SET POINT BY ZONE Code
DISPLAY
CONFORT
DISPLAY
MAINTENANCE
Ambient temperature
Set point average 3311 Yes Yes
Set point dynamic 3321 Yes Yes
Cooling Set point 3322 Yes
Heating Set point 3323 Yes
Priority of heating 3324 Yes
Reheating of Fresh Air
Enable 3331 Yes
Priority of heating 3332 Yes
Fresh Air
Set point 3312 Yes
Humidity
Dehumidification 3341 Yes
Humidification 3342 Yes
Authorisation
Free Cooling 3353 Yes
Fresh Air by CO² 3354 Yes
Refrigeration by compressor 3355 Yes
Heating by compressor 3356 Yes
Auxiliary heating 3357 Yes
Humidity Control 3358 Yes
Low noise level 3359 Yes
Other
Fan, Activate 3351 Yes
Fan, Activate, in dead zone 3352 Yes
Minimum fresh air (%) 3353 Yes Yes
Programming
Beginning of zone; each day Yes Yes
Start Uno 3211 Yes Yes
Start z.A 3212 Yes Yes
Start z.B 3213 Yes Yes
Start z.C 3214 Yes Yes
With the DS50, for each set point, to press on the key `Prg' to change the periods and to validate the good set point for the good
zone.
Note: “Monday” is considered as the first day of the week for programming the CLIMATIC™50.
Factory settings:
“Day A” activated from Monday to Saturday 6h!22h
Night mode (unoccupied) for the remaining of time, Sunday included